Open type 50Hz 200kw 250kva Cummins 6LTAA8.9-G2 engine diesel generator set

Four-stroke 50Hz 200kw 250kva Cummins 6LTAA8.9-G2 engine diesel generator set from China vendor, powered by Cummins 6LTAA8.9-G2 diesel engine, elastic coupling with Marathon alternator, optional ComAq controller, suits for prime power application. Please don’t hesitate to contact us if you have an electricity generator demand.

Technical Specifications

GENERATOR SET OUTPUT INFORMATION

Model No. Voltage Hz Phase & Wires Power Factor
(cosφ)
Standby Current
( A)
Standby Power
( KW / KVA )
Rated Power
( KW / KVA)
200GF-C50 440/254 50 3 phases 4 wires 0.8 lagging 361 220/275 200/250
200GF-C50 415/240 50 3 phases 4 wires 0.8 lagging 383 220/275 200/250
200GF-C50 400/230 50 3 phases 4 wires 0.8 lagging 397 220/275 200/250
200GF-C50 380/220 50 3 phases 4 wires 0.8 lagging 418 220/275 200/250

ENGINE SPECIFICATIONS

ENGINE PARAMETERS

Manufacturer / Model Cummins 6LTAA8.9-G2, 4-cycle
Air Intake System Turbo, air/air cooling
Fuel System P7100 type fuel pump
Cylinder Arrangement 6 inline
Engine Displacement 8.9 L
Bore*Stroke 114*145 (mm)
Compression Ration 16.6:1
Rated Speed (RPM) 1500rpm
Engine Max Power 240 KW
Governor Type Electronic

FUEL CONSUMPTION

100% Load 197 g/kw.h
75% Load 197 g/kw.h
50% Load 201 g/kw.h

LUBE SYSTEM

Lube Consumption ≤ 4 g/kw.h
Oil Pressure At Rated Speed 276-414  kPa

ALTERNATOR SPECIFICATIONS

Number Of Phases 3
Connection Type 3 phase 4 wires, Y-type connection
Bearing Numbers 1
Power Factor (cosφ) 0.8 (lagging)
Protection Grade IP23
Altitude ≤ 1000 meters
Excitation Mode Brushless, self-exciting
Insulation Grade H
Rated Capacity 250 KVA
Alternator Efficiency 92.7%

CONTROL PANEL FEATURES ( DSE7320 MKII AUTO MAINS FAILURE / UTILITY CONTROL MODULE )

Support for O-10 V & 4-20mA oil pressure senders.
Large back-lit icon LCD display.
Heated display option.
3-phase generator sensing.
3-phase generator and mains (utility) sensing
Breaker control buttons on the front fascia.
Generator & load power monitoring (kW, kV A, kV Ar, pf).
Generator overload protection (kW).
Generator/load current monitoring & protection
Configurable analogue/digital inputs.
Configurable DC, volt- free and staged loading outputs.
CAN, MPU & alternator speed sensing ( selectable depending on engine type).
Tier 4 CAN engine support.

DIMENSION & WEIGHT

Open-type size ( with base fuel tank) 2530*960*1850 (mm)
Gross Weight 2060 kg

MANUFACTURING STANDARDS

All our diesel generators are designed and manufactured in accordance with international standards, such as EN60O34, BS50O0, IEC34-1, GB755, VDE0530, CSA22.2, AS1359, as well as the requirements of ISO9001 and ISO14O01.

SUPPLY SCOPE

1. Cummins 6LTAA9.8-G2 engine
2. Alternator
3. DSE7320 MKII control panel
4. standard radiator mounted on skid
5. high-grade steel base frame (optional base fuel tank )
6. electronic governor
7. battery charger
8. cranking motor
9. English operation manual, maintenance, and test reports.
10. accessories: rubber anti-vibrator, muffler, elbow, expansion joints, battery cables, battery

NOTICE

Pictures associated with this page are for illustration only, they may not reflect the actual product, please contact us to get the actual product image. The above technical specifications are for reference only, we reserved the right to change the configuration without notifying website visitors, please contact our sales or technical team for final confirmation.

Send Inquiry


    captcha