Open type 50Hz 200kw 250kva Cummins 6LTAA8.9-G2 engine diesel generator set
Four-stroke 50Hz 200kw 250kva Cummins 6LTAA8.9-G2 engine diesel generator set from China vendor, powered by Cummins 6LTAA8.9-G2 diesel engine, elastic coupling with Marathon alternator, optional ComAq controller, suits for prime power application. Please don’t hesitate to contact us if you have an electricity generator demand.
Technical Specifications
GENERATOR SET OUTPUT INFORMATION
Model No. | Voltage | Hz | Phase & Wires | Power Factor (cosφ) | Standby Current ( A) | Standby Power ( KW / KVA ) | Rated Power ( KW / KVA) |
200GF-C50 | 440/254 | 50 | 3 phases 4 wires | 0.8 lagging | 361 | 220/275 | 200/250 |
200GF-C50 | 415/240 | 50 | 3 phases 4 wires | 0.8 lagging | 383 | 220/275 | 200/250 |
200GF-C50 | 400/230 | 50 | 3 phases 4 wires | 0.8 lagging | 397 | 220/275 | 200/250 |
200GF-C50 | 380/220 | 50 | 3 phases 4 wires | 0.8 lagging | 418 | 220/275 | 200/250 |
ENGINE SPECIFICATIONS
ENGINE PARAMETERS
Manufacturer / Model | Cummins 6LTAA8.9-G2, 4-cycle |
Air Intake System | Turbo, air/air cooling |
Fuel System | P7100 type fuel pump |
Cylinder Arrangement | 6 inline |
Engine Displacement | 8.9 L |
Bore*Stroke | 114*145 (mm) |
Compression Ration | 16.6:1 |
Rated Speed (RPM) | 1500rpm |
Engine Max Power | 240 KW |
Governor Type | Electronic |
FUEL CONSUMPTION
100% Load | 197 g/kw.h |
75% Load | 197 g/kw.h |
50% Load | 201 g/kw.h |
LUBE SYSTEM
Lube Consumption | ≤ 4 g/kw.h |
Oil Pressure At Rated Speed | 276-414 kPa |
ALTERNATOR SPECIFICATIONS
Number Of Phases | 3 |
Connection Type | 3 phase 4 wires, Y-type connection |
Bearing Numbers | 1 |
Power Factor (cosφ) | 0.8 (lagging) |
Protection Grade | IP23 |
Altitude | ≤ 1000 meters |
Excitation Mode | Brushless, self-exciting |
Insulation Grade | H |
Rated Capacity | 250 KVA |
Alternator Efficiency | 92.7% |
CONTROL PANEL FEATURES ( DSE7320 MKII AUTO MAINS FAILURE / UTILITY CONTROL MODULE )
Support for O-10 V & 4-20mA oil pressure senders.
Large back-lit icon LCD display.
Heated display option.
3-phase generator sensing.
3-phase generator and mains (utility) sensing
Breaker control buttons on the front fascia.
Generator & load power monitoring (kW, kV A, kV Ar, pf).
Generator overload protection (kW).
Generator/load current monitoring & protection
Configurable analogue/digital inputs.
Configurable DC, volt- free and staged loading outputs.
CAN, MPU & alternator speed sensing ( selectable depending on engine type).
Tier 4 CAN engine support.
DIMENSION & WEIGHT
Open-type size ( with base fuel tank) | 2530*960*1850 (mm) |
Gross Weight | 2060 kg |
MANUFACTURING STANDARDS
All our diesel generators are designed and manufactured in accordance with international standards, such as EN60O34, BS50O0, IEC34-1, GB755, VDE0530, CSA22.2, AS1359, as well as the requirements of ISO9001 and ISO14O01.
SUPPLY SCOPE
1. Cummins 6LTAA9.8-G2 engine
2. Alternator
3. DSE7320 MKII control panel
4. standard radiator mounted on skid
5. high-grade steel base frame (optional base fuel tank )
6. electronic governor
7. battery charger
8. cranking motor
9. English operation manual, maintenance, and test reports.
10. accessories: rubber anti-vibrator, muffler, elbow, expansion joints, battery cables, battery
NOTICE
Pictures associated with this page are for illustration only, they may not reflect the actual product, please contact us to get the actual product image. The above technical specifications are for reference only, we reserved the right to change the configuration without notifying website visitors, please contact our sales or technical team for final confirmation.