Silent 50Hz 1640kw 2050kva Cummins QSK60-G4 engine diesel generator set
Continuous running silent 50Hz 1640kw 2050kva Cummins engine diesel power generator set from China exporter, powered by Cummins QSK60-G4 engine, elastic coupling with original Leroy Somer alternator, optional ABB circuit breaker, suitable for Bhutan and other countries. Gosun is your reliable genset partner in China.
Technical Specifications
GENERATOR SET OUTPUT INFORMATION
Model No. | Voltage | Hz | Phase & Wires | Power Factor (cosφ) | Standby Current ( A) | Standby Power ( KW / KVA ) | Rated Power ( KW / KVA) |
1640GF-C50 | 440/254 | 50 | 3 phases 4 wires | 0.8 lagging | 2952 | 1800/2250 | 1640/2050 |
1640GF-C50 | 415/240 | 50 | 3 phases 4 wires | 0.8 lagging | 3130 | 1800/2250 | 1640/2050 |
1640GF-C50 | 400/230 | 50 | 3 phases 4 wires | 0.8 lagging | 3247 | 1800/2250 | 1640/2050 |
1640GF-C50 | 380/220 | 50 | 3 phases 4 wires | 0.8 lagging | 3418 | 1800/2250 | 1640/2050 |
ENGINE SPECIFICATIONS
ENGINE PARAMETERS
Manufacturer / Model | Cummins QSK60-G4, 4-cycle |
Air Intake System | Trubo, air / water cooling |
Fuel System | HPI PT type fuel pump |
Cylinder Arrangement | 16 in “V” |
Engine Displacement | 60.2L |
Bore*Stroke | 159*190(mm) |
Compression Ration | 14.5:1 |
Rated Speed (RPM) | 1500rpm |
Engine Max Power | 1915KW |
Governor Type | Governor control system(GCS) |
FUEL CONSUMPTION
100% Load | 193 g/kw.h |
75% Load | 191 g/kw.h |
50% Load | 196 g/kw.h |
LUBE SYSTEM
Lube Consumption | ≤ 4 g/kw.h |
Oil Pressure At Rated Speed | 345 ~ 483 kPa |
ALTERNATOR SPECIFICATIONS
Number Of Phases | 3 |
Connection Type | 3 phase 4 wires, Y type connection |
Bearing Numbers | 1 |
Power Factor (cosφ) | 0.8 (lagging) |
Protection Grade | IP23 |
Altitude | ≤ 1000 meters |
Excitation Mode | Brushless, self exciting |
Insulation Grade | H |
Rated Capacity | 2080 KVA |
Alternator Efficiency | 96.4% |
CONTROL PANEL FEATURES ( DSE7320 MKII AUTO MAINS FAILURE / UTILITY CONTROL MODULE )
Support for O-10 V & 4-20mA oil pressure senders.
Large back-lit icon LCD display.
Heated display option.
3-phase generator sensing.
3-phase generator and mains (utility) sensing
Breaker control buttons on front fascia.
Generator & load power monitoring (kW, kV A, kV Ar, pf).
Generator overload protection (kW).
Generator/load current monitoring & protection
Configurable analogue/digital inputs.
Configurable DC, volt- free and staged loading outputs.
CAN, MPU & alternator speed sensing ( selectable depending on engine type).
Tier 4 CAN engine support.
NOISE LEVEL
@ 7 meters | 68~75 DB |
DIMENSION & WEIGHT
Silent type size (40 ft high container) | 12192*2438*2896 (mm) |
Gross Weight | 22500 kg |
MANUFACTURING STANDARDS
All our diesel generator are designed and manufactured in accordance with international standards, such as EN60O34, BS50O0, IEC34-1, GB755, VDE0530, CSA22.2, AS1359, as well as the requirements of ISO9001 and ISO14O01.
SUPPLY SCOPE
1. Cummins QSK60-G4 engine
2. Alternator
3. DSE7320 MKII control panel
4. standard radiator mounted on skid
5. high grade steel base frame (optional base fuel tank )
6. electronic governor
7. battery charger
8. cranking motor
9. english operation manual, maintenance and test reports.
10. accessories: rubber anti-vibrator, muffler, elbow, expansion joints, battery cables, battery
NOTICE
Pictures associated with this page are for illustration only, they may not reflect the actual product, please contact us to get the actual product image. The above technical specifications are for reference only, we reserved the right to change the configuration without notifying website visitors, please contact our sales or technical team for final confirmation.