Open type 50Hz 12kw 15kva Perkins 403A-15G2 engine diesel generator set
Low fuel consumption 50Hz 12kw 15kva Perkins 403A-15G2 engine diesel generator set on sale, driven with Perkins 403A-15G2 diesel engine, with original Stamford alternator, optional auto transfer switch, suitable for Andorra and other countries. Gosun is your first choice power generator provider in China.
Technical Specifications
GENERATOR SET OUTPUT INFORMATION
Model No. | Voltage | Hz | Phase & Wires | Power Factor (cosφ) | Rated Current ( A) | Standby Power ( KW / KVA ) | Rated Power ( KW / KVA) |
12GF-P50 | 440/254 | 50 | 3 phases 4 wires | 0.8 lagging | 21.7 | 13.2/16.5 | 12/15 |
12GF-P50 | 415/240 | 50 | 3 phases 4 wires | 0.8 lagging | 23 | 13.2/16.5 | 12/15 |
12GF-P50 | 400/230 | 50 | 3 phases 4 wires | 0.8 lagging | 23.8 | 13.2/16.5 | 12/15 |
12GF-P50 | 380/220 | 50 | 3 phases 4 wires | 0.8 lagging | 25.5 | 13.2/16.5 | 12/15 |
ENGINE SPECIFICATIONS
ENGINE PARAMETERS
Manufacturer / Model | Perkins 403A-15G2, 4-cycle |
Air Intake System | Natural |
Fuel System | Direct injection |
Cylinder Arrangement | 3 in line |
Engine Displacement | 1.496 L |
Bore*Stroke | 84*90 (mm) |
Compression Ration | 22.5 : 1 |
Rated Speed (RPM) | 1500rpm |
Engine Max Power | 15.1KW |
Governor Type | Mechnical |
FUEL CONSUMPTION
100% Load | 250 g/kw.h |
75% Load | g/kw.h |
50% Load | g/kw.h |
LUBE SYSTEM
Lube Consumption | 0.1% ( As a percentage of fuel consumption ) |
Oil Pressure At Rated Speed | 262-359 kPa |
ALTERNATOR SPECIFICATIONS
Number Of Phases | 3 |
Connection Type | 3 phase 4 wires, Y type connection |
Bearing Numbers | 1 |
Power Factor (cosφ) | 0.8 (lagging) |
Protection Grade | IP23 |
Altitude | ≤ 1000 meters |
Excitation Mode | Brushless, self exciting |
Insulation Grade | H |
Rated Capacity | 15 KVA |
Alternator Efficiency | 81.9% |
CONTROL PANEL FEATURES ( DSE7320 MKII AUTO MAINS FAILURE / UTILITY CONTROL MODULE )
Support for O-10 V & 4-20mA oil pressure senders.
Large back-lit icon LCD display.
Heated display option.
3-phase generator sensing.
3-phase generator and mains (utility) sensing
Breaker control buttons on front fascia.
Generator & load power monitoring (kW, kV A, kV Ar, pf).
Generator overload protection (kW).
Generator/load current monitoring & protection
Configurable analogue/digital inputs.
Configurable DC, volt- free and staged loading outputs.
CAN, MPU & alternator speed sensing ( selectable depending on engine type).
Tier 4 CAN engine support.
DIMENSION & WEIGHT
Open type size | 1250*500*1100 (mm) |
Gross Weight | 370 kg |
MANUFACTURING STANDARDS
All our diesel generator are designed and manufactured in accordance with international standards, such as EN60O34, BS50O0, IEC34-1, GB755, VDE0530, CSA22.2, AS1359, as well as the requirements of ISO9001 and ISO14O01.
SUPPLY SCOPE
1. Perkins 403A-15G2 engine
2. Alternator
3. DSE7320 MKII control panel
4. standard radiator mounted on skid
5. high grade steel base frame (optional base fuel tank )
6. electronic governor
7. battery charger
8. cranking motor
9. english operation manual, maintenance and test reports.
10. accessories: rubber anti-vibrator, muffler, elbow, expansion joints, battery cables, battery
NOTICE
Pictures associated with this page are for illustration only, they may not reflect the actual product, please contact us to get the actual product image. The above technical specifications are for reference only, we reserved the right to change the configuration without notifying website visitors, please contact our sales or technical team for final confirmation.