open type 60Hz 600kw 750kva Perkins 4006-23TAG2A engine diesel generator set
Factory direct sale 60Hz 600kw 750kva Perkins 4006-23TAG2A engine diesel generator set from China vendor, driven by Perkins 4006-23TAG2A diesel engine, with Meccalte alternator, optional soundproof canopy, suitable for Saudi Arabia and other countries. GSY will always your trustworthy genset partner all over the world.
Generator Set Output Information
Model No. | Voltage | Hz | Phase & Wires | Power Factor (cosφ) | Rated Current ( A) | Standby Power ( KW / KVA ) | Rated Power ( KW / KVA) |
600GF-P60 | 480/277 | 60 | 3 phases 4 wires | 0.8 lagging | 992.3 | 660/825 | 600/750 |
600GF-P60 | 460/266 | 60 | 3 phases 4 wires | 0.8 lagging | 1035.5 | 660/825 | 600/750 |
600GF-P60 | 440/254 | 60 | 3 phases 4 wires | 0.8 lagging | 1082.6 | 660/825 | 600/750 |
600GF-P60 | 416/240 | 60 | 3 phases 4 wires | 0.8 lagging | 1145.0 | 660/825 | 600/750 |
Engine Specifications
Engine Parameters
Manufacturer / Model | Perkins 4006-23TAG2A, 4-cycle |
Air Intake System | Turbocharged, air to air charge cooled |
Fuel System | Direct injection |
Cylinder Arrangement | 6 in line |
Engine Displacement | 22.921 L |
Bore*Stroke | 160*190 (mm) |
Compression Ration | 13.6 : 1 |
Rated Speed (RPM) | 1800rpm |
Engine Max Power | 746KW |
Governor Type | Electronic |
Fuel Consumption
100% Load | 213 g/kw.h |
75% Load | 215 g/kw.h |
50% Load | 219 g/kw.h |
Lube System
Lube Consumption | 0.1% |
Oil Pressure At Rated Speed | 240 kPa |
Alternator Specifications
Number Of Phases | 3 |
Connection Type | 3 phase 4 wires, Y type connection |
Bearing Numbers | 1 |
Power Factor (cosφ) | 0.8 (lagging) |
Protection Grade | IP23 |
Altitude | ≤ 1000 meters |
Excitation Mode | Brushless, self exciting |
Insulation Grade | H |
Rated Capacity | 780 KVA |
Alternator Efficiency | 95.6% |
Control Panel Features ( DSE 6120 Auto Mains Utility Control Module )
Support for O-10 V & 4-20mA oil pressure senders.
Large back-lit icon LCD display.
Heated display option.
3-phase generator sensing.
3-phase generator and mains (utility) sensing
Breaker control buttons on front fascia.
Generator & load power monitoring (kW, kV A, kV Ar, pf).
Generator overload protection (kW).
Generator/load current monitoring & protection
Configurable analogue/digital inputs.
Configurable DC, volt- free and staged loading outputs.
CAN, MPU & alternator speed sensing ( selectable depending on engine type).
Tier 4 CAN engine support.
Dimension & Weight
Open type size ( with radiator ) | 3965*1710*2200 (mm) |
Gross Weight | 5000 kg |
Manufacturing Standards
All our diesel generator are designed and manufactured in accordance with international standards, such as EN60O34, BS50O0, IEC34-1, GB755, VDE0530, CSA22.2, AS1359, as well as the requirements of ISO9001 and ISO14O01.
Supply Scope
1. Perkins 4006-23TAG2A engine
2. Alternator
3. DSE6120 control panel
4. standard radiator mounted on skid
5. high grade steel base frame (optional base fuel tank )
6. electronic governor
7. battery charger
8. cranking motor
9. english operation manual,maintenance and test reports.
10. accessories: rubber anti-vibrator, muffler, elbow, expansion joints, battery cables, battery
Notice
Pictures associated with this page for illustration only, it may not reflect the actual product, please contact us to get actual product image. Above technical specifications for reference only, we reserved the rights to change the configuration without notify website visitors, please contact our sales or technical team for final confirmation.